Electrical Load Calculator
Size a dwelling or small commercial service with the NEC Article 220 standard method. Every demand factor is shown, so you can check each line against the Code.
Outside dimensions, living area only. 3 VA per sq ft (220.41).
1,500 VA each, min 2.
1,500 VA each, min 1.
Larger of nameplate or 5,000 VA (220.54).
Fixed appliances (VA each)
Four or more fixed appliances take a 75% demand factor (220.53). Range, dryer and HVAC are not counted here.
Only the larger of heating or cooling counts (220.60).
Demand load
32.6 kVA
32,625 VA
Service current
135.9 A
Demand VA divided by service volts
Recommended service
150 A
Next standard rating per 240.6(A)
| Load | Connected VA | Demand VA |
|---|---|---|
| General lighting and receptacles | 6,000 | - |
| Small-appliance circuits | 3,000 | - |
| Laundry circuit | 1,500 | - |
| General load after Table 220.42 demand | - | 5,625 |
| Electric range | 8,000 | 8,000 |
| Electric dryer | 5,000 | 5,000 |
| Fixed appliances (4) | 8,000 | 6,000 |
| HVAC (larger of heating or cooling) | 8,000 | 8,000 |
| Total | 39,500 | 32,625 |
Put the demand total on the panel schedule and the one-line diagram. When the schedule total and the calculation disagree, the reviewer stops trusting both documents and asks for a full reconciliation.
A planning estimate, not a stamped calculation
This tool runs the NEC 2023 Article 220 standard method on the numbers you enter. It does not replace the engineer of record, and it does not cover every load in the Code: EV charging, welders, fire pumps and other special equipment each follow their own articles. The AHJ and the engineer of record decide the final service size, and the edition your AHJ adopted governs. The 2026 NEC cuts dwelling general lighting to 2 VA per square foot for feeder and service work, so if your jurisdiction already enforces the 2026 edition, this 2023-based result will read high.
How it works
The standard method, line by line
A load calculation answers one question: how big does the service need to be? The standard method in NEC Article 220 Part III builds the answer from the connected load, then applies the demand factors the Code allows, because not everything runs at once.
For a dwelling, general lighting starts at 3 VA per square foot, which already covers the general-use receptacles, so they are not added separately. Small-appliance circuits add 1,500 VA each and the laundry circuit adds 1,500 VA. Table 220.42 then steps the combined general load down: the first 3,000 VA at 100%, the next block to 120,000 VA at 35%, and anything above that at 25%. Range, dryer, fixed appliances and the larger of heating or cooling are added after, each with its own rule.
For a small commercial building, the lighting load comes from Table 220.42(A) by occupancy, receptacles at 180 VA each take the Table 220.47 demand, and motors, kitchen equipment and signage each follow their own section. The result is a demand load in VA, converted to amps at the service voltage, and the next standard service size per 240.6(A).
Our NEC Article 220 walkthrough works the full method with a 3,000 sq ft office example, and our panel schedule guide shows how the totals land on the schedule without triggering corrections.
Worked example: 2,000 sq ft dwelling
The calculator above is prefilled with this example. Change any number and the result updates.
- General lighting, 2,000 sq ft at 3 VA
- 6,000 VA
- Small-appliance and laundry circuits
- 4,500 VA
- General load after Table 220.42 demand
- 5,625 VA
- Range, dryer, fixed appliances, HVAC
- 27,000 VA
- Total demand load
- 32,625 VA
- Service current and size, 120/240 V
- 135.9 A, 150 A service
Questions
About this calculator
Which NEC edition does this calculator follow?
NEC 2023, Article 220, standard method. The 2026 NEC moves load calculations to Article 120 and cuts the dwelling general lighting load from 3 VA to 2 VA per square foot for feeder and service work, while branch circuits stay at 3 VA per square foot. Check which edition your AHJ enforces before you submit.
Does it cover dwellings and commercial buildings?
Yes. The dwelling mode follows the Part III standard method: general lighting at 3 VA per square foot, small-appliance and laundry circuits, Table 220.42 demand, range, dryer, fixed appliances and HVAC. The small commercial mode covers one occupancy (office, retail, restaurant, warehouse or school) with Table 220.42(A) lighting loads, receptacles at 180 VA each, kitchen equipment, motors and signage, up to a 600 A service.
What does the recommended service size mean?
It is the next standard service rating at or above the calculated current, per 240.6(A). A 135.9 A demand becomes a 150 A service, not a 135.9 A one, because services are built in standard sizes. Dwellings always get at least a 100 A service.
What is not in this calculator?
EV charging, welders, fire pumps, farm loads and other special equipment each follow their own articles and are not in this tool. The engineer of record adds them, and the AHJ has the final say on the service size.
Need the stamped calculation behind the estimate?
Send your equipment list and plans. We will produce the NEC Article 220 load calculation, panel schedules and utility load letter as a permit-ready set.